8:43G-30.16 Emergency generator and water supply
(a) An emergency generator shall be provided in a room which shall have a one-hour fire rating with an approved fresh air intake and an explosion release. All machines shall be connected to the emergency generator so that all machines will operate for at least four hours following a power shutdown or outage.
(b) Water supply systems shall be designed to supply water to the fixtures and equipment on the upper floors at a minimum pressure of 15 pounds per square inch during periods when fixtures and equipment are in use.